How to use the super terminal to set the battery parameters of Smart UPS long delay models?
Problem description:
How to use the super terminal to set the battery parameters of Smart UPS long delay models.
Product line:
resolvent:
Open the super terminal, type ‘Y’, display ‘SM’. After communication is established, type ‘Shift’ and ‘>’, and the screen will display the battery parameter values. Press’ – ‘or’ Shift ‘and’+’to change the battery parameter values, and’ OK ‘will appear, indicating successful changes. Each time you press’ -‘ or ‘Shift’ and ‘+’, the battery parameters will decrease or increase by 1; Repeat the above steps until you type ‘Shift’ and ‘>’ to display the target battery parameter values, then close the HyperTerminal without saving.