Q: How to install SURT5000XLI-CH on AR201 cabinet?
A: The SURT5000XLI-CH can be installed on the AR201 cabinet by using AP9625 in conjunction with it
Q: What are the requirements for the built-in battery of SURT5000XLI-CH to power on normally?
A: The SURT5000XLI-CH starts up normally, and the built-in battery needs to meet the following requirements: 1. The voltage of the UPS built-in battery strip is above 84V; 2. The UPS built-in battery is connected normally.
Q: How to check the running time of SURT5000UXI-CH through the super terminal?
A: Connect to the super terminal, press “Y” to display SM, enter “:”, and the super terminal interface will display: “dddd:”, The current estimated operating time of UPS is XXXX minutes. UPS can be viewed by outputting “j” in online mode, bypass mode, and battery mode.
Q: How to change the bypass voltage range of SURT5000XLI-CH with a super terminal?
A: The method to change the bypass voltage range of SURT5000XLI-CH using a super terminal is as follows: Users use the original factory supplied serial port cable 940-0024 to connect UPS and computer. Open the “HyperTerminal” and select the correct communication port. The port properties are 2400/8/None/1/None. After entering the blank interface of the super terminal, press the “Enter” key to enter the main page. Press the number “1” to enter the UPS settings, select the numbers “3” and “4” to set the high bypass point and low bypass point respectively. After the settings are completed, press the “Enter” key first, enter “YES” according to the prompt on the super terminal interface to save the data, and press the “ESC” key to exit.
Q: What accessories need to be added when SURT5000XLI-CH needs to be connected with output terminal blocks?
A: When SURT5000XLI-CH needs to be connected using output terminal blocks, it is necessary to add accessory model SURT007
Q: What is the maximum number of battery packs that can be connected to SURT5000XLI-CH?
A: The maximum number of SURT192XLBP battery packs that can be connected to SURT5000XLI-CH is 10
Q: What is the model of the SURT5000XLI-CH built-in battery box?
A: RBC44, Built in 16 12V5.1AH batteries
Q: How many SURT5000UXI-CH/XLI-CH power cords are there?
A: No input power cord, 2 C1310A output power cords.