APC SURT5000 Related Questions and As (Part 2)

Q: What is the amount of heat emitted by SURT5000 during online operation?

A: The heat emitted by the online operation of SURT5000UXI-CH is 1040.00 BTU/hr, and the heat emitted by the online operation of SURT5000XLI-CH is 1057.00 BTU/hr

Q: Can the SURT3/5/6/8/10000 UXI-CH battery connection wires be shared?

A: Yes, it is possible,SURT3000UXI-CH, SURT5000UXI-CH, SURT6000UXI-CH, SURT8000UXI-CH, and SURT10000UXI-CH are all equipped with the same battery connection cable when purchased, with a diameter of 10 square millimeters, which can be shared. SURT3000XLI-CH,SURT5000XLI-CH,SURT6000XLI-CH,SURT8000XLI-CH,SURT10000XLI-CH The battery connection cable was not included with the purchase, and the battery connection cable with the same diameter that the user provided can also be shared.

Q: Can the battery connection cable included with SURT3000UXI-CH be used on SURT5000UXI-CH?

A: The battery connection cable that comes with the SURT3000UXI-CH can be used on the SURT5000UXI-CH. Similarly, SURT3000UXI-CH,SURT5000UXI-CHSURT600OUXI-CH,SURT8000UXI-CH,SURT10000UXI-CH, The randomly attached battery connection wires can be interchanged with each other. However, it should be noted that SURT3000UXI-CH, SURT5000UXI-CH, and SURT6000UXI-CH come with a battery connection cable with the host, while SURT8000UXI-CH and SURT10000UXI-CH come with two battery connection cables with the host.

Q: What are the neutral, live, and ground wires of APCSURT5000UXI-CH in battery powered or bypass state?

A: When the SURT series UPS operates in the inverter state, the live and neutral wires output are completely isolated from the input terminal through relays to prevent the front-end input from affecting the output terminal in the inverter state. When the relay is disconnected, the filtering capacitor inside the UPS suspends the output ground between zero flames. In a 220V voltage system, the voltage between the neutral wire and the ground wire at the output end/the voltage between the live wire and the ground wire is around 110VAC. When the SURT series UPS operates in bypass mode, the neutral line is straight through. The input fire and output fire are collinear. If the input zero ground voltage is 20V, then the output zero ground voltage is approximately 20V. If the input terminal voltage is 180VAC, then the output voltage under the bypass is also approximately 180VAC. The filtering components inside UPS only slightly process the input harmonic distortion and then send it to the output terminal, which is reflected in the slight difference between the output voltage value and the input voltage value, but this difference can be ignored. Applicable UPS models: SURT5000UXI-CH,SURT5000XLI-CH.