| Product datasheet |
| Specifications |
 |
Galaxy VS UPS 150kW 400V for
External Batteries, Start-up 5×8 |
| GVSUPS150KHS |
|
| Overview |
| Presentation |
Highly efficient, easy-to-deploy 150kW, 400V 3-phase UPS that brings best-in-class power protection
and low total cost of ownership to edge, small and medium data centers, as well as to critical
infrastructure in commercial and industrial applications. Includes 5×8 start-up service. See the battery
runtime chart for details. |
| Lead time Usually Ships within 2 Weeks |
| Main |
| Main Input Voltage |
400 V 3 phases |
| Other Input Voltage |
380 V
415 V |
| Main Output Voltage |
400 V 3 phases |
| Other Output Voltage |
380 V
415 V |
| Rated power in W |
150 kW |
| Rated power in VA |
150 kVA |
| Battery type |
External battery system
Li-Ion (Lithium-Ion)
VRLA |
| Provided equipment |
Dust filter |
|
|
EcoStruxure IT ready (UPS) |
|
| Installation guide |
| Integrated network management |
| Power modules ship installed |
| Start-up service |
| Batteries & Runtime |
| Battery voltage |
480…576 V DC |
| Discharge battery voltage |
384 V DC |
| Max current discharge |
407 A |
| Battery power in VAH |
0 VAh runtime |
| Extended runtime 0 |
| General |
| Bypass voltage tolerance |
+/- 10 % |
| Redundant |
No |
|
| Nov 21, 2023 |
1 |
| Physical |
| Colour |
White |
| Height |
148.5 cm |
| Width |
52.1 cm |
| Depth |
84.7 cm |
| Net weight |
290 kg |
| USB compatible |
No |
|
| Input |
| Network frequency |
40…70 Hz |
| Input voltage limits |
340…460 V 400 V |
| Maximum input current |
270 A |
| Max short time withstand
current |
65 kA |
| Input harmonic distortion |
Less than 3 % for full load |
| Load power factor |
From 0.7 leading to 0.7 lagging without any derating |
| Input Power Factor at Full Load 0.99 |
| Output |
| Maximum configurable power in
W |
150 kW |
| Output frequency |
50 Hz sync to mains
60 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised |
| Crest factor |
2.5 |
| Wave type |
Sine wave |
| Output voltage tolerance |
+/-1% after 50ms |
| Output overload operation |
10 minutes at 125% and 60 seconds at 150% |
| Bypass type |
Built-in static bypass |
| Maximum configurable power in |
150 kVA |
| VA |
| Conformance |
| Standards
Environmental |
IEC 62040-1-1
IEC 62040-2
IEC 60721-4-2 level 2M2
OSHPD
UL 1778 5th edition |
| Ambient air temperature for
operation |
0…40 °C |
| Relative humidity |
0…95 % non-condensing |
| Operating altitude |
0…3333 ft |
| Ambient air temperature for
storage |
-25…55 °C |
| Storage Relative Humidity |
10…80 % non-condensing |
| Acoustic level |
65 dBA |
|
| 2 |
Nov 21, 2023 |
| Heat dissipation |
16900 Btu/h |
| IP degree of protection IP21 |
| Communications & Management |
| Free slots |
1 |
| Control panel Touch screen LCD user interface |
| Packing Units |
| Unit Type of Package 1 |
PCE |
| Number of Units in Package 1 |
1 |
| Package 1 Height |
168 cm |
| Package 1 Width |
99 cm |
| Package 1 Length |
64 cm |
| Package 1 Weight 315 kg |
| Offer Sustainability |
| Sustainable offer status |
Green Premium product |
| REACh Regulation |
REACh Declaration |
| EU RoHS Directive |
Compliant
EU RoHS Declaration |
| Mercury free |
Yes |
| China RoHS Regulation |
China RoHS declaration |
| RoHS exemption information |
Yes |
| Environmental Disclosure |
Product Environmental Profile |
| Circularity Profile |
End of Life Information |
| Optimized Energy Efficiency |
Energy efficient product |
| Take-back
Contractual warranty |
Take-back program available |
| Warranty 1 year on-site repair or replace with factory authorized Start-Up |
| Recommended replacement(s) |
| Nov 21, 2023 |
3 |