Specifications

Product datasheet
Specifications
Symmetra PX 160kW, 400V
SY160K160H
Overview
Presentation    Modular, high-efficiency 3-phase UPS that is scalable as your data center grows up to 160kW/160kVA. Suitable for small, medium & large data center applications.
Lead time                                                        Usually Ships within 3 Weeks
Main
Main Input Voltage      400 V 3 phases
Other Input Voltage      380 V 415 V
Main Output Voltage      230 V 400 V 3 phases
Rated power in W      160000 W
Rated power in VA      160000 VA
Output connector type      Hard wire 5-wire (3P + N + E) 1
Battery type      VRLA
Provided equipment Network management card
Start-up service
User manual
Batteries & Runtime
Number of battery filled slots 15
Number of battery free slots 3
Battery recharge time 3.5 h
Number of battery replacement quantity 4
Additional information Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Battery voltage +/- 192 V (split battery referenced to neutral)
Discharge battery voltage +/- 154 V
Overcurrent protection 945 A
Maximum short-circuit current 10 kA
Max current discharge 552 A
Battery overload operation 10 minutes at 125% and 60 seconds at 150%
Battery charger power 14769 W rated
Battery design life                                     5…8 year(s)
Sep 6, 2023  1
Battery power in VAH      51840 VAh runtime
Battery option      SYBT9-B4 3 62208 VAh SYCFXR9-9 1 93312 VAh SYCFXR9-9 2 124416 VAh
Extended runtime                                       1
General
Bypass wiring configuration 5 wire (3P + N + E)
Max bypass input current 250 A
Bypass current protection 250 A
Number of power module free slots 0
Number of power module filled slots 10
Redundant Yes
Physical
Colour    Black
Height    199.1 cm
Width    180 cm
Depth    107 cm
Net weight    2812 kg
USB compatible No
Input
Network frequency 40…70 Hz
Number of input connectors 1 hard wire 5-wire (3P + N + E)
Input voltage limits 340…477 V
Maximum input current 295 A
Switching current capacity 315 A
Max short time withstand current 30 kA
Input harmonic distortion Less than 5 % for full load
Load power factor 0.5 leading to 0.5 lagging
Input Power Factor at Full Load        0.99
Output
Maximum configurable power in W 160000 W
Harmonic distortion Less than 2 %
Output frequency 50/60 Hz +/- 3 Hz user adjustable +/- 0.1 Hz sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
UPS type Double conversion online
Wave type Sine wave
Output voltage tolerance +/- 1% static and +/- 5% at 100% load step
Output harmonic distortion < 2% for 0 to 100% linear load and < 6% for full non-linear load
Output overload operation                   10 minutes at 125% and 60 seconds at 150%
      2 Sep 6, 2023
Required output current protection      250 A
Neutral output current      400 A
Bypass type      Built-in static bypass
Efficiency      94 % (in battery operation)
Maximum configurable power in 160000 VA
VA
Conformance
Product certifications      EUROBAT
Standards EN 50091-1
EN/IEC 62040-1-1
EN/IEC 62040-2
EN/IEC 62040-3
ISO 14001
ISO 9001
VFI-SS-111
Environmental
Ambient air temperature for operation 0…40 °C
Relative humidity 0…95 %
Operating altitude 0…3333 ft
Ambient air temperature for storage -15…40 °C
Storage Relative Humidity 0…95 %
Storage altitude 0.00…15240.00 m
Acoustic level 63 dBA
Heat dissipation 28741 Btu/h
NEMA degree of protection NEMA 1
IP degree of protection                           IP20
Communications & Management
Free slots    2
Preinstalled device    Network management card with CAN
Control panel    Multifunction LCD status and control console
Emergency power off                              Yes
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 214 cm
Package 1 Width 121 cm
Package 1 Length 255.4 cm
Package 1 Weight 3051 kg
Offer Sustainability
EU RoHS Directive    Not compliant
Optimized Energy Efficiency               Energy efficient product
Sep 6, 2023  3
Contractual warranty
Warranty                                                          1 year on-site repair or replace with factory authorized Start-Up
Recommended replacement(s)
     4 Sep 6, 2023
Shipping & Delivery