Specifications
Eaton UPS
DXÂ Â Â Â RTÂ Â Â Â Â 1-Â 10kVA
DX RT series UPS is specially designed by Eaton to
effectively solve the high-quality power requirements of modern IT equipment and network communication
application environments, and can be well matched with advanced modern IT equipment.
Equipped with a new generation of intelligent UPS.
Application
Environment
- Keyservers and network transmission
- ITcabinet
- Bankingand security systems
- Theoutput  powe r  facto r  is  0 . 9  (the  6K  and  10 K  models  are  as  high  as  1) ,  fu lly  matc hi ng  moder n  IT  load equipme nt.  Co mpa red  with  low  powe r  facto r  products ,  it  prov ides  mo re  active  powe r  unde r  the  same
- Adopt  on li ne  dou ble – co nversio n  to po logy ,  0ms  co nve rsio n  time ,  prov ide  high- qua lity  powe r  for  key equipme nt
- Support  pa rallel  fu nction ,  prov ide  a  highe r  level  of  powe r  protectio n  for  key  syste ms ,  ma ki ng  the syste m  re liability  greater  than  99 . 9 9%
- The  installation  height  of the  rac k  is  less  than  3U ,  sav i ng  the  inter nal  space  of  the  cabi net
-  High  efficiency  and  energysavi ng ,  sav i ng  mo re  powe r  and  heat  dissipatio n  costs  for  custo mers
- Comply with  CE  certification ,  TLC  certification  and  CQC  ce rtification
- Standard  battery  modu les  or  third- party  battery  boxes  ca n  be  co nfigu red  to  prov ide  mo re  disc harge ti me  fo r  the  load
- Compatible  with  tower  and  rack  (i n  a  sta ndard  19 -i nch  ca bi net )  insta llation ,  adapti ng  to  a  wide  ra nge of  com puter  roo m  applicatio ns  and  sav i ng  invest ment  costs
- Thechargi ng  cu r rent  of  6K  and  10 K  models  can  be  flexibly  set  th rough  the  LCD  pane l  acco rdi ng  to  the actual  batte ry  capacity  of the  custo mer ,  so  as  to  avoid  the  im pact  of  excessive  chargi ng  cu r re nt  on  the battery  life  under  the  pre mise  of  ensu r ing  the  charging  ti me
- 6K,  10 K  mode ls  have  16 / 1 7/ 18 / 1 9/2 0  adjustable  batte ry  ce lls .  Can  be  flexibly  co nfigu red  acco rding  to custo me r  needs
-  10K3: 1  models  su ppo rt  two  in put  and  output  modes :  th ree -i n put- si ngle – out  and  one -i n put- single – out
- Graphical  LCD  display ,  intuitive  display  of  UPS  status .  Easy  to  set
- The  LCD  screen  ca n  be  rotated  90  deg rees  acco rdi ng  to  the  place me nt  di rectio n
-  Provide  serial  po rt ,  USB  inte rface ,  EPO  interface ,  edita ble  dry  node  interface ,  and  prov ide  additiona l smart  s lots  for  insta lli ng  optio nal  netwo r k  card / Mod bus  card /ste m  node  ca rd  to  meet  different
- Combi ned  with  Eaton  IPM  powe r  manageme nt  software ,  it  ca n  seam lessly  integ rate  mainstrea m vi rtualizatio n  env i ro nme nt  and  cloud  ma nageme nt  tools
Model | DX RTÂ 1kVA | DX RTÂ 2kVA | DX RT 3kVA | DX RTÂ 6kVA | DXRTÂ 10KVA | DXÂ RT 3:110KVA |
power | 1000VA | 2000VA | 3000VA | 6000VA | 10kVA | 10kVA |
Input | ||||||
voltage range | 110VAC~300VAC | 110VAC~275VAC | 208-474VAC | |||
frequency range | 40~70Hz | |||||
power factor | >0.99 | |||||
harmonic wave(Â THDI) | <5% | <3% | 5% | |||
Output | ||||||
voltage | 208/220/230/240VAC(220VAC) | |||||
precision | ±2% | ±1% | ||||
frequency | 50Hz±0.05Hz(battery mode) | |||||
power factor | 0.9 | 1 | 0.9 | |||
voltage distortion | <3%(linear load) | <4%(linear load) | <1%(linear load) | <2%(linear load) | ||
overload capacity | 100%- 108% ;alarm and keep running 108% – 150% :30 secondsï¼› | 105%~ 125% ;10 minsï¼› 125%~150% ;30 secondsï¼› | 105%~ 125% ;10minsï¼› 125%~150% :30 secondsï¼› | |||
Battery | ||||||
model | Valve-regulated maintenance-free lead-acid type | |||||
Battery voltage | 36VDC | 72VDC | 96VDC | Standard UPS: 192VDC(240VDC opyional ) Long UPS:192VDC ( 192/204/216/228/240VDC adjustable ) | 384VDC | |
full load backup time (standard | >4.5min. | >4.5min. | >3min. | >4Â Â min. | >2 min. | |
Complete UPS | ||||||
efficiency | >0.9 | >0.91 | >0.91 | >0.95(online mode)/0.98(ECO mode) | 0.92(online mode)/0.97(EC0 mode) | |
static bypass | Built-in | |||||
siz e ( st an dard UPS) W * D * H mm | 443*420*87 | 443*570*87 | 443*570*87 | UPS:443*571*86.3 EBM:443*594* 130 | ||
weight (standard UPS)kg | 14.7 | 24.5 | 25.5 | UPS:13.0 EBM:45.4 | UPS:14.5 EBM:45.5 | |
siz e ( long  UPS ) W * D * H mm | 443*420*87 | 443*420*87 | 443*420*87 | 443*571*86.3 | 443*571*863 | |
weight(long UPS)kg | 7.4 | 10 | 10.1 | 13.1 | 15 | 15.5 |
noise(dB) | <45 | <50 | <50 | <55 | <60 | |
interface | Graphical LCD+LED indicator | |||||
Can add UPS | No | Yes | Yes |
communication | USB:Intelligent expansion communication slot | RS-232 ,USB,EPO,Intelligent expansion communication slot |
safety | GB4943-2001 Â IEC62040-Â 1 | |
option | Rack installation guide rail, extended battery box, PDU, SNMP/WEB card, Modbus card, AS/400 card, centralized monitoring software IPM (>10 nodes), parallel kit (above 6KVA) |
operating temperature | 0-40℃ |
humidity | <95% (no condensation) |
altitude | Less than 1000m does not derate. If more than 1000m is increased by 100m, the derate is reduced by 1% |
storage temperature | -20-55℃(without battery) |
level of protection | IP20 |