Rating (VA/W)                                              6KVA/6KW                         6KVA/6KW                      10KVA/10KW                    10KVA/10KW |
Format                                                         Tower / Rack |
Input Characteristics |
Input voltage range |
110VAC~275VAC |
Input frequency range |
40~70Hz |
Power factor |
≥ 0.995 |
Harmonic (linear load) |
<3% |
Output Characteristics |
Power factor |
1 |
Output voltage |
208 / 220 / 230 / 240VAC (default 220VAC) |
Voltage variation |
±1% |
Output frequency (battery mode) |
(50/60±0.1)Hz |
Voltage distortion (linear load) |
<1% |
Overload capacity |
105%~125% for 10 minutes; 125%~150% for 30 seconds |
Battery Characteristics |
Type |
Valve-controlled maintenance-free lead-acid type |
|
Battery voltage |
16pcs default
(20pcs optional) |
192VDCÂ default
(192/Â 204/Â 216/Â 228/Â 240VDC adjustable) |
16pcs default
(20pcs optional) |
192VDCÂ default
(192/Â 204/Â 216/Â 228/
240VDC adjustable) |
Backup time – Full load/ 50% load (PF=0.9) |
4Â minutes /Â 11Â minutes |
depends on battery |
2Â minutes / 8Â minutes |
depends on battery |
Charger current |
0~4A (default 1.6A) |
0~12AÂ (default 4A) |
0~4A (default 2A) |
0~12AÂ (default 4A) |
UPS Characteristics |
Efficiency                                                     double conversion mode 95%; ECO mode 98% |
Maintenance bypass switch                            Built-in |
Dimensions W x D x H / Weight |
Dimensions (mm) |
443 x 570 x 87
EBM 443 x 593 x 129 |
443 x 570 x 87 |
443 x 570 x 87
EBM 443 x 593 x 129 |
443 x 570 x 87 |
Weight (kg) |
13.0
EBM 45.5 |
13.1 |
14.5
EBM 45.5 |
15.0 |
Operating conditions, Standards and Approvals |
Display |
Graphical LCD + LED indicator |
Operating temperature |
0 to 40°C |
Humidity |
0 ~ 95% (no condensation) |
Altitude |
<1000m no derating, >1000m derating 1% for every 100m |
Storage temperature |
-20 to 55°C (without battery) |
Protection level |
IP20 |
Parallel |
Support 3 units |
Communication |
RS232 /Â USB /Â Network-M2/Â INDGW-M2/Â Relay-MSÂ cards |
Options |
Rack mounting rail, EBM, PDU, centralized monitoring software IPM, parallel kit |
Approvals |
CE |