Product datasheet |
Specifications |
|
Galaxy VS UPS 150kW 400V for
External Batteries, Start-up 5×8 |
GVSUPS150KHS |
|
Overview |
Presentation |
Highly efficient, easy-to-deploy 150kW, 400V 3-phase UPS that brings best-in-class power protection
and low total cost of ownership to edge, small and medium data centers, as well as to critical
infrastructure in commercial and industrial applications. Includes 5×8 start-up service. See the battery
runtime chart for details. |
Lead time Usually Ships within 2 Weeks |
Main |
Main Input Voltage |
400 V 3 phases |
Other Input Voltage |
380 V
415 V |
Main Output Voltage |
400 V 3 phases |
Other Output Voltage |
380 V
415 V |
Rated power in W |
150 kW |
Rated power in VA |
150 kVA |
Battery type |
External battery system
Li-Ion (Lithium-Ion)
VRLA |
Provided equipment |
Dust filter |
|
|
EcoStruxure IT ready (UPS) |
|
Installation guide |
Integrated network management |
Power modules ship installed |
Start-up service |
Batteries & Runtime |
Battery voltage |
480…576 V DC |
Discharge battery voltage |
384 V DC |
Max current discharge |
407 A |
Battery power in VAH |
0 VAh runtime |
Extended runtime 0 |
General |
Bypass voltage tolerance |
+/- 10 % |
Redundant |
No |
|
Nov 21, 2023 |
1 |
Physical |
Colour |
White |
Height |
148.5 cm |
Width |
52.1 cm |
Depth |
84.7 cm |
Net weight |
290 kg |
USB compatible |
No |
|
Input |
Network frequency |
40…70 Hz |
Input voltage limits |
340…460 V 400 V |
Maximum input current |
270 A |
Max short time withstand
current |
65 kA |
Input harmonic distortion |
Less than 3 % for full load |
Load power factor |
From 0.7 leading to 0.7 lagging without any derating |
Input Power Factor at Full Load 0.99 |
Output |
Maximum configurable power in
W |
150 kW |
Output frequency |
50 Hz sync to mains
60 Hz sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised |
Crest factor |
2.5 |
Wave type |
Sine wave |
Output voltage tolerance |
+/-1% after 50ms |
Output overload operation |
10 minutes at 125% and 60 seconds at 150% |
Bypass type |
Built-in static bypass |
Maximum configurable power in |
150 kVA |
VA |
Conformance |
Standards
Environmental |
IEC 62040-1-1
IEC 62040-2
IEC 60721-4-2 level 2M2
OSHPD
UL 1778 5th edition |
Ambient air temperature for
operation |
0…40 °C |
Relative humidity |
0…95 % non-condensing |
Operating altitude |
0…3333 ft |
Ambient air temperature for
storage |
-25…55 °C |
Storage Relative Humidity |
10…80 % non-condensing |
Acoustic level |
65 dBA |
|
2 |
Nov 21, 2023 |
Heat dissipation |
16900 Btu/h |
IP degree of protection IP21 |
Communications & Management |
Free slots |
1 |
Control panel Touch screen LCD user interface |
Packing Units |
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
168 cm |
Package 1 Width |
99 cm |
Package 1 Length |
64 cm |
Package 1 Weight 315 kg |
Offer Sustainability |
Sustainable offer status |
Green Premium product |
REACh Regulation |
REACh Declaration |
EU RoHS Directive |
Compliant
EU RoHS Declaration |
Mercury free |
Yes |
China RoHS Regulation |
China RoHS declaration |
RoHS exemption information |
Yes |
Environmental Disclosure |
Product Environmental Profile |
Circularity Profile |
End of Life Information |
Optimized Energy Efficiency |
Energy efficient product |
Take-back
Contractual warranty |
Take-back program available |
Warranty 1 year on-site repair or replace with factory authorized Start-Up |
Recommended replacement(s) |
Nov 21, 2023 |
3 |