Product data sheet |
Specifications |
|
Galaxy VS UPS 50kW 400V for up
to 4 internal 9Ah smart modular
battery strings, Start-up 5×8 |
GVSUPS50K0B4HS |
Overview |
Presentation |
Highly efficient, easy-to-deploy 50kW, 400V 3-phase UPS that brings best-in-class power protection
and low total cost of ownership to edge, small and medium data centers, as well as to critical
infrastructure in commercial and industrial applications. This UPS is for up to 4 smart modular high
capacity battery strings, but is supplied without batteries, so you can easily customize the battery
runtime. Includes 5×8 start-up service. |
Lead time Usually Ships within 2 Weeks |
Main |
Main Input Voltage |
400 V 3 phase |
Other Input Voltage |
380 V
415 V |
Main Output Voltage |
400 V 3 phase |
Other Output Voltage |
380 V
415 V |
Kw Rating |
50 kW |
Rated power in VA |
50 kVA |
Battery Type |
Internal modular battery
VRLA |
Provided equipment |
Dust filter |
|
|
Installation manual |
|
Integrated network management |
Start-Up Service |
EcoStruxure Ready |
Batteries & Runtime |
Battery voltage |
480V |
End of Discharge Battery
Voltage |
384 V |
End of Discharge Maximum
Battery Current |
136 A |
Battery power in VAH |
0 VAh runtime |
Extendable Run Time
General |
0 |
Redundant |
No |
|
Oct 8, 2023 |
1 |
Physical |
Color |
White |
Height |
58.46 in (148.5 cm) |
Width |
20.51 in (52.1 cm) |
Depth |
33.35 in (84.7 cm) |
Net Weight |
440.92 lb(US) (200 kg) |
USB compatible |
No |
|
Input |
Input Frequency |
40 – 70 Hz |
Efficiency at full load |
340…460 V 400 V |
Maximum Input Current per
Phase |
90 A |
Maximum Short Circuit
Withstand (Icw) |
65 kA |
Input Total Harmonic Distortion |
Less than 3% for full load |
Load power factor |
From 0.7 leading to 0.7 lagging without any derating |
Input Power Factor at Full Load 0.99 |
Output |
Max Configurable Power (Watts) |
50 kW |
Harmonic distortion |
Less than 3% |
Output Frequency (sync to
mains) |
50 Hz sync to mains
60 Hz sync to mains |
Crest factor |
2.5 |
Waveform Type |
Sine wave |
Output voltage tolerance |
+/- 5% after 2ms
+/-1% after 50ms |
Output Voltage THD |
< 1% linear load and < 3% non-linear load |
Overload Operation |
10 minutes @ 125% and 60 seconds @ 150% |
Bypass type |
Built-in Static Bypass |
Maximum configurable power in 50 kVA |
VA |
Conformance |
Standards
Environmental |
IEC 62040-1-1
IEC 62040-2
OSHPD |
Ambient Air Temperature for
Operation |
32…104 °F (0…40 °C) |
Relative Humidity |
0…95 % non-condensing |
Operating altitude |
0…3300 ft |
Ambient Air Temperature for
Storage |
5…104 °F (-15…40 °C) |
Storage Relative Humidity |
10…80 % non-condensing |
Storage altitude 0…10000 ft (0.00…3048.00 m) |
2 |
Oct 8, 2023 |
Acoustic level |
61 dBA |
Heat dissipation |
6151 Btu/h |
IP degree of protection IP20 |
Communications & Management |
Control panel Touch Screen LCD User Interface |
Ordering and shipping details |
GTIN |
731304410072 |
|
Packing Units |
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
66.14 in (168 cm) |
Package 1 Width |
38.98 in (99 cm) |
Package 1 Length |
25.20 in (64 cm) |
Package 1 Weight 440.92 lb(US) (200 kg) |
Offer Sustainability |
Sustainable offer status |
Green Premium product |
REACh Regulation |
REACh Declaration |
EU RoHS Directive |
Compliant
EU RoHS Declaration |
Mercury free |
Yes |
China RoHS Regulation |
China RoHS declaration |
RoHS exemption information |
Yes |
Environmental Disclosure |
Product Environmental Profile |
Circularity Profile |
End of Life Information |
Optimized Energy Efficiency |
Energy efficient product |
Take-back
Contractual warranty |
Take-back program available |
Warranty 1 year on-site repair or replace with factory authorized Start-Up |
Recommended replacement(s) |
Oct 8, 2023 |
3 |